How often do terminal HEPA Filters need to be changed?
Recommendation

Thursday, 12 February 2026 9 .00 - 17.00 h
Best Practice for Manual and Automated Visual Inspection of Parenterals
HEPA filters (H13 and H14) are usually used as terminal filters in cleanrooms, cleaning the supplied air to the required particulate purity. Only if these filters function properly, a cleanroom can have the required purity. For this reason, these filters are subject to regular inspection and must be replaced when necessary.
Here also lies the answer to the question of how often these filters must be replaced: when necessary.
It is necessary if:
- damage is found in the filter or on the filter seal during the leakage test
- the pressure loss at the filter exceeds a filter resistance specified for the ventilation system
But: the measurement of the filter resistance does not replace the filter integrity test!
An interval defined by the company operating a clean air system is possible from a GMP point of view, but no general interval can be defined, since the increase in pressure loss depends on:
- the aerosol concentration of the environment
- the type and number of prefilters
- the interval between pre-filter replacements
Companies that determine the regular replacement of filters in internal SOPs do so because of a risk consideration - avoiding to miss the time when the filter replacement would have been necessary. However, a correctly installed and correctly operated HEPA filter can be used for 10 years or more.
Related GMP News
04.02.2026Endotoxins Testing: Potential Change for WFI and Steam in the USP
04.02.2026Microbiological Deviations and Technical Deficiencies - Warning Letter to US Manufacturer
28.01.2026Changes to the 'Water Monographs' in the European Pharmacopoeia
21.01.2026Deficient Water System: Warning Letter to US Manufacturer
17.12.2025FDA publishes new Draft Guideline on GMP for Medical Gases
10.12.2025VDI 6022 Sheet 8.1 published: Qualification for the cleaning of air-conditioning systems


